Over-current protection is provided by tripping the relay when motor operating current(In) exceeds over-current setting(Is) of EOCR for a period greater than the preset operating time (O-Time).


During a phase loss, the motor winding current may increase by 150% or more. As the motor winding current increase, the winding temperature may also increase and possibly damage the winding insulation. The quick trip time on EOCR helps to prevent over-current damage to the windings.


Indication LED on the dial plate provides trip indication and ammeter function. The LED starts to flash at the current point where motor current is equal to current setting level (Is), so user can verify motor current with reading the scale of LOAD adjustment on the dial plate.
This also provides an accurate current setting. LED is illuminated during motor current exceeds current setting (Overloading Status). After tripping is occured, the LED keeps on until relay is reset. The trip indication also an important feature in a multiple relay & contractor (starter) installation.


EOCR has a wide current adjustment range over 10:1. It enables three types of model to cover the widest range from 0.1A up to 600A and inventory control to be much easier.


Motors that require only one-third or one-fourth the relay capability can use the same size relay by looping wires 2 or 3 times.
Each additional loop will increase the current measured by one time of the single loop.

Straight-through-Wiring

Looping Option (1-Loop)

No. of Loops
Time of Passing
Current Set. Range (A)
0.5 Type
0
1
0.50-6.0A
Looping Option
1
2
0.25-3.0A
2
3
0.17-2.0A
3
4
0.12-1.5A
4
5
0.10-1.2A


0.5 type of each model fitted to an external current transformer can achieve higher ampere ranges. (E. CT Option)

Type
Current ratio of E. CT.
Current Setting Range
05
-
0.5-6A
E. CT Option
100
100:5
10-120A
200
200:5
20-240A
300
300:5
30-360A
400
400:5
40-480A
500
500:5
50-600A
600
600:5
60-720A

External CT Option



Pushing RESET button on the dial plate or interrupting power supply provides manual instantaneous reset.
Electrical remote reset is also provided by panel-mounted Reset button.


EOCR-SS uses only 250mA of power, much less than thermal bimetallic overload relays. The result is significant cost savings over the life of relays (20 times cost saving).


G-43, DLF Indl. Estate-1, Faridabad - 121003, Haryana (INDIA)
Phone no. : 91-129-2278256, 2273860 Fax no. : 91-129-2273850
© Concord Automation and Controls, India epowered by Abacusdesk