Model
|
FDS
|
Over
Current Setting
* Each current type is adjusted by DIP Switch
Setting. (SW5-SW8)
|
Type
|
Setting
Range
|
05
|
1-5A
|
20
|
4-20A
|
100
|
10-120A
|
150
|
15-180A
|
200
|
20-240A
|
300
|
30-360A
|
400
|
40-480A
|
500
|
50-600A
|
600
|
60-700A
|
Instantaneous
Over-current Setting
|
300-1800%
of Is
|
Ground
Fault Current Setting
|
-
|
Alert
Setting
|
-
|
Start
Time Setting
(D-Time)
|
SW3-On
(Inverse)
|
0-120
Sec
|
SW3-Off
(Definite)
|
1-120
Sec
|
Trip
Time Setting
(O-Time)
|
SW3-On
(Inverse)
|
1-30
Sec
|
SW3-Off
(Definite)
|
0.3-25
Sec
|
Control
Voltage
|
85-250
VAC/DC
|
Output
Relay
|
Relay
1
|
OL
Relay
|
2-SPST,
5A/250VAC Resistive
Normally Energized
|
Relay
2
|
Short
Circuit Relay
|
1-SPST,
5A/250VAC Resistive
Normally De-energized
|
Time
Characteristics
|
SW3-On
|
Inverse
|
SW3-Off
|
Definite
|
Troubleshooting
/ Trip Indication
|
Seven
Segment LED Display
|
Current
Sensing
|
3-CT
|
Mounting
|
DCU
|
Flush
|
PCU
|
35mm
Din Rail /Panel
|
Connection
|
Interface
Cable
|
*DCU:
Display & Control Unit
*PCU: Power Control Unit |