CAC
now offers its latest range of Time Delay Relays in
Technical collaboration with COMAT AG of Switzerland.
These new range of ECO Timers are manufactured
at our state of the art production facility and conform
to the latest IEC specifications.
This new range of Multifunction Timers incorporate multiple
functions including On delay, Off delay, Blinker etc.
in one model with time setting range upto 12 hours and
all at an economical price.
Separate models for Star Delta applications are also
available.
|

|
|
General
Data |
Mechanical
Data |
Case
|
DIN
case (DIN 43 880) WHD=22.5X90X70mm
|
Protection
|
IP
40, terminals IP 20
|
Case
material
|
NORYL
SE1 (UL 94V-1)
|
Weight
|
approx.
80g
|
Mounting
|
TS
35 DIN/EN 50022
|
Jolt
resistance
|
IEC
68-2-6/FC, IEC 571
|
Connections
|
Terminals
with guard 2x1.5 mm², 1x2.5 mm²
|
Tightening
torque
|
≤
0.8 Nm
|
Ambient
conditions |
Storage
temperature |
-40°C
to +85°C |
Operating
temperature |
-25°C
to +60°C |
Relative
humidity |
10
to 95% non-condensing |
Electrical
data |
Supply |
Operating
voltage nominal / type |
230V
AC |
115V
AC |
24V
DC |
Operating
voltage range |
184V
to 265V 50 Hz |
95V
to 138V 50 Hz |
18V=
to 30V= |
180V
to 255V 60 Hz |
90V
to 132V 60Hz |
|
Frequency
range |
48Hz
to 62Hz |
48Hz
to 62Hz |
|
Current
consumption IB |
≤
30mA
50 Hz |
≤
35mA
50 Hz |
≤
25mA |
≤
35mA
60 Hz |
≤
40mA
60 Hz |
|
Power
consumption |
≤
1.2W,7
VA |
≤
1
W, 5 VA |
≤
0.85
W |
Inrush
current |
≤
1.8A,
t=100µs |
≤
1A,
t=150µs |
≤
1.5A,
t=250µs |
Switch-off
energy, inductive parallel load |
5
KV/50mWs/1 Hz, or single pulse 2.5 kV / 0.5Ws |
Transient
voltage protection (EN 61000-4-5, surge) |
2kV |
2kV |
1
kV |
Time
Response |
Time
Ranges |
|
ECO-31
|
ECO-32
|
Time
Ranges |
0.5
sec to 5 sec / 2 sec to 20 sec / 16 sec to 160 sec
/ 2 min to 20 min |
0.1
sec to 1.2 sec / 1 sec to 12 sec / 0.1 min to 1.2
min / 1 min to 12 min / 0.1 hr to 1.2 hr / 1 hr
to 12 hr |
Range
tolerance tmin |
-30%
to 0% |
Range
tolerance tmax |
0
to +20% |
Fine
setting (potentiometer) |
1:10 |
Dependency
on ambient conditions |
Operating
voltage/Type |
230V
AC |
115V
AC |
24V
DC |
Voltage
stability |
±
0.1% / K (≤
0.5%) |
±
0.1% / K (≤
0.5%) |
±
0.1% / K (≤
0.5%) |
|
-0.2%
/K (≤
2%) |
-0.2%
/K (≤
2%) |
-0.2%
/K (≤
2%) |
Max.
deviation for parasitic induction defined under
7.2 |
≤
2% |
≤
2% |
≤
2% |
Other
time data |
Supply
failure protection |
≥30ms
|
≥
30ms |
≥30ms
|
Reset
time |
≤
100
ms |
≤
100
ms |
≤
100
ms |
Repeat
accuracy |
±
0.2% (± 20ms) |
±
0.2% (± 20ms) |
±
0.2% (± 10ms) |
Output
circuit |
Output |
1xU,
contact AgNi |
Switching
voltage |
5
to 250V~/5 to 60V= |
Switching
current |
6A/20A/20
ms |
Breaking
capacity |
1500VA
AC1//... 170W |
Recomm.
minimum load |
10mA
12V |
Service
life mechanical |
≥
2x107 |
Service
life electrical |
≥
1x105/6A, 230V AC1 |
≥
3.5x105/3A, 230V AC1 |
≥
1x105/5.5A, 30V DC1 |
≥
3.5x105/3A, 30V DC1 |
Insulation |
≥
2kV / 1 min |
|
|
|
|
ECO
31
|
ECO
32
|
|
On
Delay
S>>R on with delay
S OFF >> R off |
|
|
|
One
Shot Leading Edge
S>>R on for t
S OFF>>R off |
|
|
|
Blinker
S>>R on/off periodically according to t
S OFF >> R off |
|
|
|
Off
Delay
S>>R on
S OFF>>R off with delay |
|
|
|
Pulse
Shaping
S (pulse or continous contact)>> R on for
t |
|
|
|
One
shot trailing edge
S OFF >> R on for t
S on for t >> R off |
|
|
|
|
|
|